Product introduction
KFR-1 super thin fire-resistive coating is made by our company.They are first super thin fire-resistive coating in China.It is made by new technique.It will form a protective foamed char layer when exposing to fire.The foamed char layer can prevent heat from fire and prevent steel construction softening in a period time.This product is widely applied to steel structure in the industrial buildings,such as gymnasium,airport,Hotel,School,cinema,restaurant,post,telecommunication,Financial center,commercial building,industrial workshop,underground buildings,etc.
Features
Having thin layer and excellent and efficient fire protection.
Due to acrylic functional resin as binder,the coating has excellent anti-aging capacity and doesn’t pulverize within 30 years.
Easy to use.No toxic,and safe for storing and shipping;
Excellent decoration affect,lots of colors for choosing;
Application
Application temperature 0-50℃ ,relative humidity<=85%,needed to according to the dry condition to do multiple application(need to avoid exporting to raining and sun);the coating thickness should be application by the rule of fire protection
The applied surface needed to be clean to make sure no oil,no dust and need to check the compatibility of the anti-corrosive substrates with fire-resistive coating.
Painting,spray,rolling paint can be used and the coating should be stirred completely before applying,It needs professional people to do the application guidebook.
It is better to finish when the seal is opened,for the left.
Storage and transportation
Shelf life: 12 months from date of delivery in unopened containers,prevented from sunlight and fires should be seal tightly.
It is better to be used with BF-2 protection paint for fire-resistive coating,the usage amount 0.18-0.36/m2
Main technical indicator | |||||
Item | Indicator | ||||
State in container | no lump,homogeneous after strring | ||||
Drying time(surface drying,h) | <=8 | ||||
Adhesive strenght(Mpa) | >=0.2 | ||||
Water resistance(h) | >=24,the coating is no peeling or falling | ||||
Freeze-thaw-stabily(times) | >=15,the coating is no peeling or falling | ||||
Anti-cracking performance at primary of drying | no cracking | ||||
Fire-resistance performance | Coating thickness(mm) | 0.4 | 0.7 | 1.2 | 1.9 |
Fire-retardant ratings(min) | >=30 | >=60 | >=90 | >=120 |
Declaration:the relevant data the specification sheet is gaine by experiments and operation experience and can be used as application guide. The coating is only suitable for professional use ,not for other use and application. We only guarantee the quality of product in correct use.